Take 6 minutes to read this article
The CentricsIT engineering experts are here to help with your data center in our monthly FixIT column. This month, learn how to access and clear system error logs to address attention lights on HP Integrity servers. Below, our engineers walk you through an example on how to first show the log, then select event, and finally select Text to make the log more readable. You can also clear the logs using the C command.
If you need additional assistance, contact us to talk about our on-demand engineering options.
[mp] MP> SL
Event Log Viewer Menu:
Log Name Entries % Full Latest Timestamped Entry
—————————————————————————
E – System Event 741 72 % 21 Jan 2012 04:14:32
F – Forward Progress 4000 100 %
B – Current Boot 148 49 %
P – Previous Boot 18 6 % 23 Jul 2010 08:35:20
C – Clear All Logs
L – Live Events
Enter menu item or [Ctrl-B] to Quit: e
Log Name Entries % Full Latest Timestamped Entry
—————————————————————————
E – System Event 741 72 % 21 Jan 2012 04:14:32
Event Log Navigation Help:
+ View next block (forward in time, e.g. from 3 to 4)
– View previous block (backward in time, e.g. from 3 to 2)
Continue to the next or previous block
D Dump the entire log
F First entry
L Last entry
J Jump to entry number
H View mode configuration – Hex
K View mode configuration – Keyword
T View mode configuration – Text
A Alert Level Filter options
U Alert Level Unfiltered
? Display this Help menu
Q Quit and return to the Event Log Viewer Menu
Ctrl-B Exit command, and return to the MP Main Menu
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >T
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 740: 21 Jan 2012 04:14:32
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3BA8022E50 FFFF0007F40A0300
Log Entry 739: 21 Jan 2012 04:14:04
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3B8C022E40 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 738: 21 Jan 2012 04:13:36
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3B70022E30 FFFF0007F40A0300
Log Entry 737: 21 Jan 2012 04:13:07
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3B53022E20 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 736: 21 Jan 2012 04:12:38
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3B36022E10 FFFF0007F40A0300
Log Entry 735: 21 Jan 2012 04:12:09
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3B19022E00 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 734: 21 Jan 2012 04:11:39
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3AFB022DF0 FFFF0007F40A0300
Log Entry 733: 21 Jan 2012 04:11:10
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3ADE022DE0 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 732: 21 Jan 2012 04:10:42
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3AC2022DD0 FFFF0007F40A0300
Log Entry 731: 21 Jan 2012 04:10:13
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3AA5022DC0 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 730: 21 Jan 2012 04:09:44
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3A88022DB0 FFFF0007F40A0300
Log Entry 729: 21 Jan 2012 04:09:16
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3A6C022DA0 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 728: 21 Jan 2012 04:08:48
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3A50022D90 FFFF0007F40A0300
Log Entry 727: 21 Jan 2012 04:08:20
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3A34022D80 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 726: 21 Jan 2012 04:07:52
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3A18022D70 FFFF0007F40A0300
Log Entry 725: 21 Jan 2012 04:07:24
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A39FC022D60 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 724: 21 Jan 2012 04:06:56
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A39E0022D50 FFFF0007F40A0300
Log Entry 723: 21 Jan 2012 04:06:28
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A39C4022D40 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >
Log Entry 722: 21 Jan 2012 04:05:42
Alert Level 2: Informational
Keyword: COOLING_UNIT_OK
Cooling unit OK
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to OK
0x204F1A3996022D30 FFFF0007F40A0300
Log Entry 721: 21 Jan 2012 04:05:13
Alert Level 3: Warning
Keyword: COOLING_UNIT_WARNING
Cooling unit warning
Logged by: Baseboard Management Controller;
Sensor: Cooling Device – System Fan 5
Data1: transition to Non-Critical from OK
0x204F1A3979022D20 FFFF0107F40A0300
MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >