Take 6 minutes to read this article

The CentricsIT engineering experts are here to help with your data center in our monthly FixIT column. This month, learn how to access and clear system error logs  to address attention lights on HP Integrity servers. Below, our engineers walk you through an example on how to first show the log, then select event, and finally select Text to make the log more readable. You can also clear the logs using the C command.

If you need additional assistance, contact us to talk about our on-demand engineering options. 

[mp] MP> SL

Event Log Viewer Menu:

Log Name            Entries    % Full      Latest Timestamped Entry

—————————————————————————

E – System Event          741        72 %      21 Jan 2012 04:14:32

F – Forward Progress     4000       100 %

B – Current Boot          148        49 %

P – Previous Boot          18         6 %      23 Jul 2010 08:35:20

C – Clear All Logs

L – Live Events

Enter menu item or [Ctrl-B] to Quit: e

Log Name            Entries    % Full      Latest Timestamped Entry

—————————————————————————

E – System Event          741        72 %      21 Jan 2012 04:14:32

Event Log Navigation Help:

+       View next block     (forward in time,  e.g. from 3 to 4)

–       View previous block (backward in time, e.g. from 3 to 2)

Continue to the next or previous block

D       Dump the entire log

F       First entry

L       Last entry

J       Jump to entry number

H       View mode configuration – Hex

K       View mode configuration – Keyword

T       View mode configuration – Text

A       Alert Level Filter options

U       Alert Level Unfiltered

?       Display this Help menu

Q       Quit and return to the Event Log Viewer Menu

Ctrl-B  Exit command, and return to the MP Main Menu

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >T

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 740: 21 Jan 2012 04:14:32

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3BA8022E50 FFFF0007F40A0300

Log Entry 739: 21 Jan 2012 04:14:04

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3B8C022E40 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 738: 21 Jan 2012 04:13:36

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3B70022E30 FFFF0007F40A0300

Log Entry 737: 21 Jan 2012 04:13:07

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3B53022E20 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 736: 21 Jan 2012 04:12:38

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3B36022E10 FFFF0007F40A0300

Log Entry 735: 21 Jan 2012 04:12:09

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3B19022E00 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 734: 21 Jan 2012 04:11:39

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3AFB022DF0 FFFF0007F40A0300

Log Entry 733: 21 Jan 2012 04:11:10

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3ADE022DE0 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 732: 21 Jan 2012 04:10:42

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3AC2022DD0 FFFF0007F40A0300

Log Entry 731: 21 Jan 2012 04:10:13

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3AA5022DC0 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 730: 21 Jan 2012 04:09:44

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3A88022DB0 FFFF0007F40A0300

Log Entry 729: 21 Jan 2012 04:09:16

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3A6C022DA0 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 728: 21 Jan 2012 04:08:48

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3A50022D90 FFFF0007F40A0300

Log Entry 727: 21 Jan 2012 04:08:20

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3A34022D80 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 726: 21 Jan 2012 04:07:52

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3A18022D70 FFFF0007F40A0300

Log Entry 725: 21 Jan 2012 04:07:24

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A39FC022D60 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 724: 21 Jan 2012 04:06:56

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A39E0022D50 FFFF0007F40A0300

Log Entry 723: 21 Jan 2012 04:06:28

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A39C4022D40 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >

Log Entry 722: 21 Jan 2012 04:05:42

Alert Level 2: Informational

Keyword: COOLING_UNIT_OK

Cooling unit OK

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to OK

0x204F1A3996022D30 FFFF0007F40A0300

Log Entry 721: 21 Jan 2012 04:05:13

Alert Level 3: Warning

Keyword: COOLING_UNIT_WARNING

Cooling unit warning

Logged by: Baseboard Management Controller;

Sensor: Cooling Device – System Fan 5

Data1: transition to Non-Critical from OK

0x204F1A3979022D20 FFFF0107F40A0300

MP:SL (+,-,,D, F, L, J, H, K, T, A, U, ? for Help, Q or Ctrl-B to Quit) >